Product Description
Description
Battery and PV Inverter Specifications
Battery Input Specifications
Battery Chemistry: Lithium-Ion (Li-Ion)
Compatible Battery Voltage Range: 160VDC to 800VDC
Maximum Charging Current: 50A (per input)
Maximum Discharging Current: 50A (per input)
Number of Battery Inputs: 2
Charging Strategy for Li-Ion Battery: Self-adjusts according to Battery Management System (BMS) signals
PV String Input Specifications
Maximum DC Input Power: 65,000W
Maximum DC Input Voltage: 1,000VDC
Startup Voltage: 180VDC
MPPT Voltage Range: 150VDC to 850VDC
Full Load DC Voltage Range: 450VDC to 850VDC
Rated DC Input Voltage: 600VDC
PV Input Current per String: 36A (4 strings in total)
Maximum PV Current (Isc) per String: 55A (4 strings in total)
Number of Maximum Power Point (MPP) Trackers: 4
Strings per MPP Tracker: 2
AC Output Specifications
Rated AC Output and Uninterruptible Power Supply (UPS) Power: 50,000W
Maximum AC Output Power: 55,000W
Rated AC Output Current: 75.8A (at 380VAC) / 72.5A (at 400VAC)
Maximum AC Current: 83.3A
Maximum Continuous AC Pass-Through: 150A
Peak Power for Off-Grid Operation: 1.5 times the rated power, sustained for 10 seconds
Generator Input: 75.8A
Smart Load Capacity: 150A
AC Coupling Current: 75.8A
Power Factor: Adjustable from 0.8 Leading to 0.8 Lagging
Output Frequency and Voltage: 50/60Hz; Three-phase 220/380VAC, 230/400VAC
Grid Type: Three-Phase
Environmental Limits
Operating Temperature Range: -40°C to 60°C
Cooling System: Intelligent Cooling (Sound level below 45 dB)
Communication with Battery Management System: RS485 / CAN protocols
Ingress Protection Rating: IP65 (Dust-tight and protected against low-pressure water jets)
Safety Certifications: Complies with IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 standards